Technical indicators
1, the device work power: the world's general input (85-265VAC) or DC 220VDC, power consumption <4W
2, communication interface: RS485, baud rate 9600
3, phase measurement error: <0.01 °
4, closing phase error: <1.5 °
5, closing time before the closing range: 0.01S ~ 15.0S
6, switch closing time setting range: 0.1S ~ 5.0S
7, the whole step LED indicates the phase error: <± 2.5 °
8, the frequency measurement error: <0.01Hz; frequency to determine the error: <0.02Hz
9, PT input voltage range: 0 ~ 150Vac
10, the voltage difference set range: 0.5 ~ 6.0%
11, low-voltage lockout, set the range: 10 ~ 90%
12, the voltage measurement error: the voltage display value and the standard voltage meter absolute error <0.1%; the relative error of the voltage on both sides <0.1%
13, closing output contact capacity: 30A, 250Vac / 30Vdc
14, FM, regulator output contact capacity: 5A / 250Vac, 0.5A / 220Vdc
15, the parameters can be set online, parameter setting range see the settings parameter table